Single channel signal conditioning instrument for level detection for NAMUR sensors

Technical Data:

Series Module unit for mounting on carrier rails,35 x 7.5 acc. to EN 50022/60715
Connection terminals
Type of terminal Screw terminal
Wire cross-section 0.25 mm2 (AWG 23) … 2.5 mm2 (AWG 12)
Nominal voltage AC 24 … 230 V (-15 %, +10 %) 50/60 Hz
Nominal voltage DC 24 … 65 V DC (-15 %, +10 %)
Max. power consumption 2 W (8 VA)
Sensor input
Quantity 1 x NAMUR
Input type Active (sensor power supply by VEGATOR 111)
Measured value transmis-
sion
Analogue 1.2/2.1 mA
Switching threshold

On

Off

Tolerance

1.5 mA
1.7 mA
± 100 μA
Current limitation Through internal resistance
Terminal voltage 8.2 V DC, ± 5 %
Internal resistance 1 kΩ, ± 1 %
Detection line break ≤ 0.05 mA
Detection shortcircuit ≥ 6.8 mA
Relay output
Quantity 1 x operating relay, 1 x fail safe relay(optional)
Contact Floating spdt
Switching voltage min. 10 mV DC, max. 253 V AC/50 V DC
Switching current min. 10 μA DC, max. 3 A AC, 1 A DC
Breaking capacity min. 50 mW, max. 500 VA, max. 54 W DC
Basic delay 100 ms
Ambient conditions
Ambient temperature at the installation site of the
instrument
-20 … +60 °C (-4 … +140 °F)
Protection rating IP 20
up to 2000 m (6562 ft) above sea level II
up to 5000 m (16404 ft) above sea level II – Only with connected overvoltage protection
up to 5000 m (16404 ft) above sea level I
Degree of soiling 2