Vibrating level switch with tube extension for liquids

Technical Data:

Process pressure -1 … +64 bar/-100 … +6400 kPa (-14.5 … +928 psig)The function of the instrument is en- sured up to an operating pressure of 100 bar/10000 kPa (1450 psig) at maximum process temperature of +50 °C (+122 °F) (only with threaded versions).
Process temperature -50 … +250 °C (-58 … +482 °F)
Viscosity – dynamic 0.1 … 10000 mPa s
Density 0.7 … 2.5 g/cm³ (0.025 … 0.09 lbs/in³); 0.5 … 2.5 g/cm³ (0.018 … 0.09 lbs/in³) by switching over
Ambient temperature -40 … +70 °C (-40 … +158 °F)
Hysteresis approx. 2 mm (0.08 in) with vertical instal- lation
Process fitting Threads from G¾, ¾ NPT, flanges from DN 25, 1″, hygienic fittings
Operating voltage for connection to an amplifier according to NAMUR IEC 60947-5-6, approx. 8.2 V
Off-load voltage U 0 approx. 8.2 V
Short-circuit Current consumption I U approx. 8.2 mA
Ʋ Falling characteristics ≥ 2.2 mA uncovered/≤ 1 mA covered
Ʋ rising characteristics ≤ 1 mA uncovered/≥ 2.2 mA covered
Ʋ Fault message ≤ 1 mA
SIL qualification Optionally up to SIL2