VEGASWING 51/53 VEGASWING 61/63 VEGASWING 66
Application Liquids Liquids Liquids under high and
low temperatures
Version VEGASWING51:
Compact version
VEGASWING61:
Compact version
Compact version or with tube
extension up to 3 m
Material 316L 316L, ECTFE, PFA,enamel,Alloy
400, Duplex, Alloy C22
Inconel 718 (tuning fork), 316L,Alloy C22
Process fitting Thread from G1⁄2, 1⁄2 NPT,hygienic fittings Thread from G3⁄4, 3⁄4 NPT,flanges from DN 25, 1″,hygienic fittings Thread from G1, 1 NPT,flanges from DN 50, 2″
Process temperature -40 … +150 °C -50 … +250 °C -196 … +450 °C
Process pressure -1 … +64 bar
(-100 … +6400 kPa)
-1 … +64 bar
(-100 … +6400 kPa)
-1 … +160 bar
(-100 … +16000 kPa)
Signal output Transistor output,contactless electronic switch,IO-Link Relay, transistor, two-wire,
NAMUR output,
contactless electronic switch
Relay, transistor, two-wire output
Approvals VEGASWING 51:Overfill protection, Ship, CSA-OL

VEGASWING 53:Overfill protection, Ship, CSA-OL,EHEDG, 3-A, FDA, EG 1935/2004

ATEX, IEC, FM, CSA, EAC (GOST),
UKR Sepro, Overfill protection,
Ship, SIL2, KOSHA, NEPSI,
INMETRO
ATEX, IEC, CSA, EAC (GOST),
UKR Sepro, Overfill protection,
steam boiler, Ship, SIL2, KOSHA,
NEPSI, INMETRO, VdTÜV 100
Benefit ▪ Minimal time and cost expenditure thanks to simple setup without medium
▪ Accurate and reliable function through medium-independent switching point
▪ Minimal costs for maintenance and servicing