Technical specifications:

Type Control unit for location in a non-hazardous area
Gas and ranges see transmitter type for gas name, measuring range and units
Inputs all configuration via PC or laptop
4 to 20 mA transmitter with 2- or 3-core cable
Outputs Alarm 1, Alarm 2 and Fault as standard
Warning and inhibit relays on optional relay module
Single, common or voted alarms on optional relay module
Acknowledgeable relays on optional relay module
Display Dräger REGARD ® 3900 and Dräger REGARD ® 3910 4 lines, 40 characters back-lit LCD
4 LEDs per channel (function, fault, Alarm 1 alarm 2)
DC and AC power supply LEDs
Inhibit-LED
Dräger REGARD ® 3920 Large graphic display (4 x 62 mm, 64 x 128 pixel)Menu structure and messages in real text
3 push button navigation
4 LEDs per channel (function, fault, Alarm 1 alarm 2)
DC and AC power supply LEDs
Inhibit-LED
Power supply External 24 VDC Internal 110 / 240 VAC, 50 / 60 Hz
Dimensions (W x H x D) Dräger REGARD ® 3900 and 3920 ca. 420 x 300 x 190 mm
Dräger REGARD ® 3910 ca. 300 x 225 x 20 mm
Weight ca. 3 kg, depending upon type and installed power supply
Ambient conditions Temperature 0 to 55 °C
Pressure 700 to 1,300 hPa
Humidity 0 to 100 % r.F., non-condensating
Protection class IP 65
Housing material ABS OV
Approvals* ATEX II (2) G, TRL 06 ATEX 21099X
SIL SIL 1
CE-Zeichen Electromagnetic Compability (Directive
89/336/EWG)
DNV/GL only Dräger REGARD ® 3910
MED B+D only Dräger REGARD ® 3910