Technical specifications:

Type Explosion proof UV/IR flame detector for hydrocarbon-based fuel and gas fires
Spectral Response UV = 0.185 – 0.260 μm
IR = 4.4 – 4.6 μm
Measuring Performance Field of view Horizontal 100°; Vertical 95°
Response Time Typically 3 seconds. 200 msec to flash fire
Detection Range(at highest Sensitivity Setting for 1 ft 2 (0.1 m 2 ) pan fire) Fuel ft / m
n-Heptane / Gasoline 93 / 28
Diesel Fuel / JP5 / Kerosene 70 / 21
Methanol 57 / 17
IPA (Isopropyl Alcohol) 70 / 21
Ethanol 95 % 57 / 17
Polypropylene Pellets 60 / 18
Office Paper 33 / 10
LPG* 60 / 18

* 30″ (0.75 m) high, 10″ (0.25 m) width plume fire

Electrical Data:

Output Signals 0 – 20 mA (stepped), HART ®
Fault Signal 0 +1 mA
BIT Fault Signal 2 mA ±10 %
Normal Signal 4 mA ±10 %
Warning Signal 16 mA ±5 %
Alarm Signal 20 mA ±5 %
Relays Alarm, Fault and Auxiliary
SPST volt-free contacts rated 2 A at 30 VDC
RS485 Modbus compatible communication link
Power supply 24 VDC nominal (18 – 32 VDC)
Power Consumption Standby: Max. 90 mA (110 mA with heated window)
Alarm: Max. 130 mA (160 mA with heated window)

 

Ambient Conditions:

Temperature -55 to +75 °C / -67 to + 167 °F (operating)
-55 to +85 °C / -67 to + 185 °F (option and storage)
Humidity Up to 95 % non-condensing
(withstands up to 100 % RH for short periods)

 

Enclosure:

Material Stainless steel SS 316L
Material option Heavy duty copper free aluminum, red epoxy enamel finish
Connecting thread 2 x 3/4″ – 14 NPT or 2 x M25 x 1.5 mm
Weight Detector SS 316L 2.8 kg / aluminum 1.3 kg
Tilt mount 1.0 kg
Dimensions Detector 101.6 x 117 x 157 mm
Ingress Protection IP66 and IP67, NEMA 250 6P

Approvals:

ATEX and IECEx Ex II 2 G D                      –                   –
Ex db eb op is IIC T4 Gb Ex db eb op is IIC T4 Gb Ex db eb mb op is IIC T4 Gb
Ex tb op is IIIC T 96 °C Db Ex tb op is IIIC T 106 °C Db Ex tb op is IIIC T 98 °C Db
(Ta -55 °C to +75 °C) (Ta -55 °C to +85 °C) (Ta -55 °C to +75 °C)
FM/FMC/CSA Class I Div. 1, Groups B, C & D
Class II/III Div. 1, Groups E, F & G
Safety Integrity Level SIL2 certified by TÜV (EN 61508)
Performance Approval EN 54-10 (VdS)
FM 3260
CE marking EMI/RFI protected to EN 61326-3 and EN 61000-6-3